Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM01639
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/06/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK FINAL |
|
08/04/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FINISH CONDUIT AND BOND BUSHINGS ON ROOF |
|
08/01/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* ROOF: 1. SUPPORT EMT AS PER CODE 2. SHEETMETAL THREAD SCREWS NOT ALLOWED FOR GROUNDING - 250.8 3. CLEAN SURFACE UNDER LUG 250.12 4. ONLY ONE CONDUCTOR PER TERMINAL LUG 5. BOND CONTACTOR ENCLOSURE BUILDING 1. FINISH EXIT LIGHTING |
|