Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T07CM01635
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/21/2007 | FIRE - FINAL | Approved | ALL PROBLEMS TAKING CARE OF | |
09/04/2007 | FIRE - FINAL | Denied | REMOVE SLIDE BOLTS FROM FRONT EXIT. REMOVE EXIT SIGN BY MECH./STOREAGE AREA. PUT DIRECTIONAL EXIT SIGN FOR 2ND EXIT. NEED PANIC HARDWARE ON SECOND EXIT. HAVE A SPR. CONTRACTOR ADD A SPR. HEAD TO NEW OUTSIDE CEILING IN BREAK AREA OR REMOVE THE CEILING. | |
08/08/2007 | FIRE - FINAL | Denied | NEED AN ANNUAL SPR. REPORT FOR THE ENTIRE COMPLEX. REMOVE SLIDE BOLTS FROM FRONT EXIT. NORTH EXIT CANNOT BE THROUGH STOCK OR MECH. AREA. SOUTH EXIT DOORS MUST SWING IN DIRECTION OF EGRESS. EXIT DOORS OTHER THAN FRONT EXIT MUST HAVE PANIC HARDWARE. SOUTH EXIT NEEDS DIRECTIONAL EXIT SIGNS. |