Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/24/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/21/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PANEL DIRECTORY TO BE NEAT, LEGIBLE AND CORRECT USE PANEL DIRECTORY PROVIDE, DO NOT COVER #'S |
|
| 08/09/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* STILL NEED TO FIX G.E.C PARTIAL INSPECTION GO THROUGH UNIT WHERE IS INSTA-HOT? 1. ROMEX NOT ALLOWED ABOVE SUSPENDED CEILING - NEC 334.12 2. SECURE FIXTURES TO GRID - NEC 300.11 3. LOFT RECEPTACLE DEAD, 4-WAY SWITCH TRIPS BREAKER 4. AT CONDENSOR - STRAP FLEX WITHIN 12" OF TERMINATIONS, EXTERIOR LIGHT & RECEPTACLE NOT WORKING, IDENTIFY DISCONNECT 5. PANEL DIRECTORY NOT CORRECT - NEC 408.4 ALSO, TO BE NEAT/LEGIBLE 6. WIRING NOT PER PLAN 7. NEED LISTED FAN BOXES FOR CEILING FANS - NEC 314.27D 8. OVERFILLED WIRENUTS & LOOSE GROUND SCREWS IN J-BOX -- NEC 110.3 B |
|
| 07/24/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* WORK IN PROGRESS ALSO, NEED TO REPAIR/REPLACE GROUNDING ELECTRODE AND BONDING CONDUCTORS FOR SERVICE (STOLEN) |