Permit: T07CM01633

Parcel: 107144300


Addresses:

2569 N 1ST AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/24/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/21/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PANEL DIRECTORY TO BE NEAT, LEGIBLE AND CORRECT
USE PANEL DIRECTORY PROVIDE, DO NOT COVER #'S
08/09/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
STILL NEED TO FIX G.E.C
PARTIAL INSPECTION GO THROUGH UNIT

WHERE IS INSTA-HOT?

1. ROMEX NOT ALLOWED ABOVE SUSPENDED CEILING -
NEC 334.12
2. SECURE FIXTURES TO GRID - NEC 300.11
3. LOFT RECEPTACLE DEAD, 4-WAY SWITCH TRIPS BREAKER
4. AT CONDENSOR - STRAP FLEX WITHIN 12" OF TERMINATIONS, EXTERIOR LIGHT & RECEPTACLE NOT WORKING, IDENTIFY DISCONNECT
5. PANEL DIRECTORY NOT CORRECT - NEC 408.4
ALSO, TO BE NEAT/LEGIBLE
6. WIRING NOT PER PLAN
7. NEED LISTED FAN BOXES FOR CEILING FANS - NEC 314.27D
8. OVERFILLED WIRENUTS & LOOSE GROUND SCREWS
IN J-BOX -- NEC 110.3 B
07/24/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
WORK IN PROGRESS
ALSO, NEED TO REPAIR/REPLACE GROUNDING ELECTRODE AND BONDING CONDUCTORS FOR SERVICE (STOLEN)