Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/24/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 06/18/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER WALLS, BATH HARD LIDS |
|
| 06/13/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) USE PROPER CRIMP TOOL FOR CRIMP SLEEVES NEC 110.3 B 2) PROVIDE NAIL PLATES 1 1/4 OR LESS FROM STUD FACE NEC 300.4 3) SEAL UNUSED OPENINGS IN BOXES NEC 314.17 A 4) ELECTRICAL NOTES ARE FOR A RESIDENCE, NOT COMMERCIAL-REVISE TO SHOW ACTUAL SCOPE OF WORK AND WIRING METHOD 5) GROUND ALL METAL BOXES, GROUND TO WRAP MINIMUM 2/3 RDS AROUND SCREW AND TIGHTEN NEC 250.4 6) INSTALL ALL MUD RINGS 7) WIRING NOT COMPLETE/HANGING WIRES 8) WATER BOND CLAMP TO BE ACCESSIBLE 9) IDENTIFY WHITE USED AS HOT IN SWITCH LEGS NEC 200 10) WIRING NOT PER PLAN 11) WORK TO BE DONE BY ELECTRICAL CONTRACTOR |