Permit: T07CM01632

Parcel: 118041460


Addresses:

1630 S SAN JOSE DR

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
01/07/2008 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
01/04/2008 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FASCIA BOARD AT REAR OF HOUSE MISSING NAILS
2) ALL OUT RIGGER 2 X 4 CALL FOR 3-120 NAILS AT EACH END
3) SHEARWALL AT S.E. CORNER GARAGE NOT NAILED 6" ON CENTER AT CONNECTION WITH HOLDOWN
4) HOLDOWN NOT ON PROPER SHEARWALL S.E. CORNER OF BAY WINDOW
5) NEED TO CLIP ALL BOTTOM CHORDS TO TOP PLATE AT LEAST 48" ON CENTER
6) OK TO DRY IN ROOF