Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/29/2007 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 10/17/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ACCESSIBLE ENTRANCE 2. TEMPORARY DOOR TO BE REMOVED 3. SHOWER HEAD MOUNT (HEAD TO BE ON 60" HOSE) TO BE 38" TO 48" ABOVE SHOWER FLOOR 4. INSTALL ALL HANDRAILS PER ANSI 117.1 IN ACCESSIBLE RESTROOM 5. CLOSET FLANGE IS TOO CLOSE TO WALL. SHOULD BE 16" TO 18" FROM WALL TO CENTER 6. HALL SUPPOSED TO BE 42" WIDE AT EXIT 7. OPENING INTO OFFICE SHOULD BE 32" MINIMUM 8. REAR DOOR REQUIRES EXTERIOR LANDING, ACCESSIBLE THRESHOLD AND ACCESSIBLE RAMP 9. PLAN DIMENSIONS PP A1.0 AND DETAILS ARE CORRECT THEY JUST WEREN'T FOLLOWED |