Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM01608
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/17/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
07/24/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROPERLY IDENTIFY NEW UNITS AT PANEL DIRECTORY AND UNITS DISCONNECTS -- NEC 408.4, 110 AC #1, #2, ETC 2. DISCONNECTS TO HAVE PROPER FRONT & ENTRY WORKING CLEARANCE, MIN 36" -- NEC 110.26 3. INSTALL PROPERLY SIZED EQUIPMENT GROUNDING CONDUCTOR TO DISCONNECT - NEC 250.122 4. PROVIDE GFI PROTECTED SERVICE RECEPTACLE ON ROOF FOR UNITS - NEC 210.63 |
|
06/14/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |