Permit: T07CM01608

Parcel: 11105076B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM01608

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/17/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/24/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROPERLY IDENTIFY NEW UNITS AT PANEL DIRECTORY AND UNITS DISCONNECTS -- NEC 408.4, 110 AC #1, #2, ETC
2. DISCONNECTS TO HAVE PROPER FRONT & ENTRY WORKING CLEARANCE, MIN 36" -- NEC 110.26
3. INSTALL PROPERLY SIZED EQUIPMENT GROUNDING CONDUCTOR TO DISCONNECT - NEC 250.122
4. PROVIDE GFI PROTECTED SERVICE RECEPTACLE ON ROOF FOR UNITS - NEC 210.63
06/14/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*