Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM01595
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/27/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
11/05/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK PHARMACY AREA WHEN EMERGENCY LIGHTING TEST IS COMPLETE, CALL THIS FINAL INSPECTION IN AGAIN AND PROVIDE WRITTEN RESULTS OF TEST. |
|
11/01/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR PANEL & FEEDERS 1. PLAN SHOW #600 KC MIL CU TO PANEL "BC" 2. NEED MINIMUM #3 CU FOR 400 AMP EQUIPMENT GROUND - NEC 250.122 3. STRAP "3BE" FEEDER RACEWAY WITHIN 36" OF GEAR 4. SEAL UNUSED RACEWAYS OUT OF PANELS 5. EMERGENCY LIGHTING TO BE TESTED AND APPROVED EITHER BY CITY OF TUCSON OR BY WRITTEN LETTER FROM HOSPITAL THAT STATES IT HAS BEEN TESTED AND WORKING PER PLAN 6. FIRE ALARM SYSTEM DEVICES DO NOT APPEAR TO BE LOCATED PER PLAN? CANNOT FIND HORN/STROBE "M" NOTE? PARTIAL INSPECTION ONLY |
|
10/30/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* ELECTRICIAN TO BE ON SITE TO OPEN EQUIPMENT ALSO, PROVIDE LAST WRITTEN REPORT FOR THE TESTING OF THE EMERGENCY SYSTEMS. |