Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM01595
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/21/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
10/25/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILING TILES IN PHASE 1 OF PHARMACY AREA CKTS (2) STILL LEFT TO BE ALTERED WILL BE LOOKED AT WHEN COMPLETED. |
|
10/23/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REMOVE TEMPORARY WIRING FROM CEILING 2. CLOSE UP UNUSED OPENINGS 3. FINISH/PROPERLY SUPPORT LOW VOLTAGE WIRING 4. HAVE BROKEN COUPLING ON EMT BY BATHROOM 5. INSTALL VAV J-BOX COVERS 6. STILL HAVE CKT'S TO BE CHANGED OVER |
|
10/22/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* WORK CALLED IN BEFORE COMPLETE |