Permit: T07CM01595

Parcel: 11615088L

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T07CM01595

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
02/21/2008 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
10/25/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILING TILES IN PHASE 1 OF PHARMACY AREA
CKTS (2) STILL LEFT TO BE ALTERED WILL BE LOOKED AT WHEN COMPLETED.
10/23/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REMOVE TEMPORARY WIRING FROM CEILING
2. CLOSE UP UNUSED OPENINGS
3. FINISH/PROPERLY SUPPORT LOW VOLTAGE WIRING
4. HAVE BROKEN COUPLING ON EMT BY BATHROOM
5. INSTALL VAV J-BOX COVERS
6. STILL HAVE CKT'S TO BE CHANGED OVER
10/22/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
WORK CALLED IN BEFORE COMPLETE