Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T07CM01588
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/17/2007 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 07/13/2007 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) MARKED ON DINING ROOM FLOOR, INSTALL BLK UNDER HOLE 2) GARAGE S/E SIDE TOWARD FRONT GABLE END TRUSS NOT SHOWN ON PLAN AS DRAG TRUSS, RUN OSB UP TO ROOF DECK 3) REAR SHEAR 1ST FLOOR AT PATIO, RENAIL BOTTOM OF OSB TO PLATE, NEED RETRO, P. A. HAS A BEND AT PLATE LINE, OTHER P.A. NAILED INTO JOINT OF STUDS NOT GOOD 3) AT ROOF NEED FLASHING BACKING REAR WALL AT BOTTOM PLATE 4) NEED WIND BRACE REAR ALL 2ND FLOOR 5) ASK ROOFER ABOUT CRICKET AT TOWER WALL ROOF 6) NAIL C.C. PLY RIPPER NEXT TO TOWER MARKED IN BLACK 7) MISSED BLKS, NOT NAILED VERY GOOD, SHORT CUT AT ROOF HIP JOINTS |