Permit: T07CM01568

Parcel: 126071530


Addresses:

4001 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM01568

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/29/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/28/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
FINISH ITEMS #6, 8, 11, 12
08/27/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
DO NOT OCCUPY AREA WITHOUT FINAL C OF O

1. MANUFACTURES CLIPS TO BE EFFECTIVE
2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RINGS 314.20
3. CAP & BOX FUTURE EQUIPMENT WHIPS
4. SUPPORT VDV - COAX - 815.6, 820.6
ALSO, SPEAKER 725.6
5. PROPERLY SEAT GROUND WIRES UNDER SCREWS & INSTALL COVERS
6. LABEL PANEL DIRECTORIES AS PER 408.4
7. GROUND FIXTURE HARDWARE
8. MAINTAIN WORKING CLEARANCES AT AC DISCONNECTS 110.26 ALSO COMPRESSOR/PUMP
9. TIGHTEN LOOSE FITTINGS
10. EXPOSED OPENING BEHIND DISCONNECT WITH CONDUCTORS AGAINST DRYWALL
11. PLEASE VERIFY LISTING FOR FLEX RACEWAY
12. EXIT LIGHTING TO BE ON AREA SERVED 700.12
13. 1 EXIT LIGHT NOT WORKING
14. USE APPROVED WIRING METHODS FOR WALL LIGHTS