Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/29/2007 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 08/01/2007 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* OK PREVIOUS ITEMS EXCEPT AS NOTED 1. PLAN REVISION 2. MAST BRACE 3. SUPPORT VDV CABELING 725.6, 810.6 4. SUPPORT M/C 12" OF BOXES 5. BOX OVERFILL |
|
| 07/31/2007 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* 1) TIGHTEN GROUND LUGS 2) IDENTIFY GROUNDING CONDUCTOR 3) BOND MYERS HUB 4) PLANS STILL NOT REFLECTIVE OF WORK INSTALLED 5) PLEASE VERIFY BOND FOR TEMP POWER-OK TO CLEAR IF BONDED |
|
| 07/25/2007 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BOND CLOSE NIPPLE PER NEC 250.92 & 250.102 2. INSTALL PROPER MAST CLAMP CANNOT USE MINNIE 3. GROUNDING ELECTRODE CONDUCTOR TO BE TERMINATED ON NEUTRAL BASE 4. SERVICE NOT INSTALLED PER APPROVED DRAWINGS. PROVIDE APPROVED REVISION OR INSTALL PER PLANS. |