Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM01568
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/29/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/05/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. NEED LETTER FOR USE OF PVC IN WALLS 2. ALL OTHER PREVIOUS INSPECTION ITEMS CORRECTED |
|
| 07/02/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. VDV CABELING NOT TO BE SUPPORTED OFF OF M/C CABLE 2. SUPPORT VDV CABELING DOWN WALLS & PROTECT FROM SHARP METAL EDGES 3. PROTECT M/C CABLES AT TOP PLATES 4. PROTECT AND SUPPORT PVC CONDUIT IN WALLS 5. PLANS DO NOT ALLOW PVC CONDUIT IN WALLS |
|
| 06/11/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* OK PVC CONDUIT FOR DATA OK IMC FOR DENTAL CHAIRS |
|
| 06/08/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. FINISH CONDUIT INSTALLATION 2. PLEASE ADD 02010 TO PERMIT |