Permit: T07CM01559

Parcel: 107080630


Addresses:

840 W KELSO ST

Inspection Status: Approved

Inspection History: REINFORCED MASONRY PRE-GROUT

Date Description Inspector Results Comments
06/05/2007 REINFORCED MASONRY PRE-GROUT Approved IVRS - Inspection :*
06/04/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) OK TO GROUT-EXCEPT FOR BATHROOM PLUMBING NEEDS TO BE WRAPED AND INSPECTED BEFORE THEY FILL LOSE CELLS
05/29/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) FIRST 48" LIFT OK
05/23/2007 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) VERTICAL REBAR REQUIRED EACH SIDE WINDOW AND DOOR JAMBS
2) VERTICAL REBAR TO OVERLAP REBAR PROTRUDING FROM SLAB
3) CANNOT HAVE PLASTIC PLUMBING PIPING EMBEDDED IN MASONRY
4) STOPPED INSPECTION