Permit: T07CM01554

Parcel: 12810080A

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/13/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) OK FOR FINAL
06/08/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PERMANENTLY I.D UNITS W/SUITE #
2. EXTEND COVERS OVER CANVAS CONNECTORS TO COVER ALL CANVAS
3. MARK UNIT DATA PLATE W/PROPER HEAT STRIP & FUSE ACCORDINGLY.
4. PROVIDE CONDENSATE DRAINS
5. PROVIDE AIR BALANCE REPORT
05/24/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. FINISH WORK ON ROOF.
2. PROVIDE AIR BALANCE.
3. ALL EXPOSED DUCT ON THE ROOF PROVIDE MIN. 2" DUCT LINER.