Permit: T07CM01553

Parcel: 12810080A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM01553

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/15/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/22/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
ATM NOT LISTED AS AN ELECTRICAL SIGN UNDER SIGN PERMIT AND NOT INSPECTED AS SUCH. SHOULD BE UNDER BUILDING PERMIT AS PART OF ATM SIGNAGE. SHOULD MEET REQUIREMENTS OF ARTICLE 600
ALSO, NEEDS TO BE LISTED AND LABELED BY A "NRTL"
08/17/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. SIGN ABOVE ATM NEEDS TO MEET REQUIREMENTS OF
NEC 600
2. RE-OPEN SIGN PERMIT IF THIS SIGN IS UNDER THAT PERMIT
SIGN NEVER INSPECTED BY RICK HOLLANDER
07/05/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. UNABLE TO LOCATE PLAN, PERMIT OR INSPECTION HISTORY
2. INSPECTOR REQUIRES IMMEDIATE ACCESS TO ALL AREAS
3. CONTINUED "NOT READY" WILL RESULT IN A
REINSPECTION FEE

- PULL PERMIT FOR SIGN ABOVE ATM OR MEET THE REQUIREMENTS OF NEC ART. 600 WHICH REQUIRES SIGN TO BE LISTED AND LABELED AT A ELECTRICAL SIGN.
06/20/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK TEMP C OF O
1. SIGN ABOVE ATM TO BE LISTED AS SIGN & NEEDS TO MEET REQUIREMENTS OF NEC 600
2. PROVIDE INSTALLATION INSTRUCTIONS FOR ATM
NEED TO SEE LISTING MARK
3. COMPLETE ITEMS FROM PREVIOUS INSPECTION
06/19/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. COMPLETE ITEM 1 FROM INSPECTION ON 6/11/07
2. RECALL AFTER ATM INSTALLED IN BUILDING
3. NEED LISTING ON LIGHT & SIGNAGE EQUIPMENT FOR ATM INSTALLED IN BUILDING
06/11/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. PROVIDE LISTING INFORMATION ON DRIVE UP ATM
DO NOT HAVE PROPER WORKING CLEARANCES ON PANEL LOCATED INSIDE ATM. THIS IS PERTAINING TO ATM ENCLOSURE.
2. NEED DETAILED PANEL SCHEDULES
06/08/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
ROOF
1. STRAP LIQUID TIGHT ON ROOF WITHIN 12" OF CONNECTIONS AND EVERY 3' BETWEEN
2. MAX. FUSE SIZE EXCEEDED FOR UNIT HP-1
3. HPCU-2 HAS DIFFERENT SIZE FUSE INSTALLED IN EACH LEG
04/20/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*