Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM01553
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/15/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/22/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* ATM NOT LISTED AS AN ELECTRICAL SIGN UNDER SIGN PERMIT AND NOT INSPECTED AS SUCH. SHOULD BE UNDER BUILDING PERMIT AS PART OF ATM SIGNAGE. SHOULD MEET REQUIREMENTS OF ARTICLE 600 ALSO, NEEDS TO BE LISTED AND LABELED BY A "NRTL" |
|
08/17/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SIGN ABOVE ATM NEEDS TO MEET REQUIREMENTS OF NEC 600 2. RE-OPEN SIGN PERMIT IF THIS SIGN IS UNDER THAT PERMIT SIGN NEVER INSPECTED BY RICK HOLLANDER |
|
07/05/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. UNABLE TO LOCATE PLAN, PERMIT OR INSPECTION HISTORY 2. INSPECTOR REQUIRES IMMEDIATE ACCESS TO ALL AREAS 3. CONTINUED "NOT READY" WILL RESULT IN A REINSPECTION FEE - PULL PERMIT FOR SIGN ABOVE ATM OR MEET THE REQUIREMENTS OF NEC ART. 600 WHICH REQUIRES SIGN TO BE LISTED AND LABELED AT A ELECTRICAL SIGN. |
|
06/20/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK TEMP C OF O 1. SIGN ABOVE ATM TO BE LISTED AS SIGN & NEEDS TO MEET REQUIREMENTS OF NEC 600 2. PROVIDE INSTALLATION INSTRUCTIONS FOR ATM NEED TO SEE LISTING MARK 3. COMPLETE ITEMS FROM PREVIOUS INSPECTION |
|
06/19/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. COMPLETE ITEM 1 FROM INSPECTION ON 6/11/07 2. RECALL AFTER ATM INSTALLED IN BUILDING 3. NEED LISTING ON LIGHT & SIGNAGE EQUIPMENT FOR ATM INSTALLED IN BUILDING |
|
06/11/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. PROVIDE LISTING INFORMATION ON DRIVE UP ATM DO NOT HAVE PROPER WORKING CLEARANCES ON PANEL LOCATED INSIDE ATM. THIS IS PERTAINING TO ATM ENCLOSURE. 2. NEED DETAILED PANEL SCHEDULES |
|
06/08/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* ROOF 1. STRAP LIQUID TIGHT ON ROOF WITHIN 12" OF CONNECTIONS AND EVERY 3' BETWEEN 2. MAX. FUSE SIZE EXCEEDED FOR UNIT HP-1 3. HPCU-2 HAS DIFFERENT SIZE FUSE INSTALLED IN EACH LEG |
|
04/20/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |