Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
09/24/2007 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
09/21/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
09/20/2007 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
09/17/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
- SUPPORT FLEX DUCTS EVERY 5'
- INSTALL FLEX DUCTS PER DETAILS ON PLANS
- I.D FAN COILS
- PROVIDE AUDIBLE & VISIBLE ALARMS FOR DUCT SMOKE DETECTORS.
- RELOCATE SUPPLY DIFFUSER BLOCKING ACCESS TO
FAN COIL #2
- EXTEND RETURN AIR BOOT HIGHER FOR PROPER FLEX DUCT CONNECTION IN RECEPTION AREA
08/30/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
PROVIDE MIN. 1/8" PER FT SLOPE ON CONDENSATE DRAIN LINES