Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/24/2007 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 09/21/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 09/20/2007 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 09/17/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* - SUPPORT FLEX DUCTS EVERY 5' - INSTALL FLEX DUCTS PER DETAILS ON PLANS - I.D FAN COILS - PROVIDE AUDIBLE & VISIBLE ALARMS FOR DUCT SMOKE DETECTORS. - RELOCATE SUPPLY DIFFUSER BLOCKING ACCESS TO FAN COIL #2 - EXTEND RETURN AIR BOOT HIGHER FOR PROPER FLEX DUCT CONNECTION IN RECEPTION AREA |
|
| 08/30/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* PROVIDE MIN. 1/8" PER FT SLOPE ON CONDENSATE DRAIN LINES |