Permit: T07CM01517

Parcel: 140292040


Addresses:

3675 E BRITANNIA DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/21/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/23/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK LIST EXCEPT PANEL CRA REPLACE CHASE NIPPLE WITH CLOSE NIPPLE OR INSTALL LOCKNUT
01/08/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. LABEL ALL PANELS, SCHEDULES, EQUIP. DISCONNECTS
2. PROVIDE OR INSTALL INSULATING BUSHING AT PANEL M3 FOR CONNECTOR AT TOP OF PANEL PER 300 NEC, #4 OR LARGER
3. OPEN J-BOX IN ELECTRIC ROOM FOR INSPECTION PROVIDE LIFT
4. MECH. LUGS NOT INSTALLED TO GROUND BUS PROPERLY
IN "DB-S" CANNOT STACK ON TOP OF EXISTING LUGS.
5. INSTALL BOND BUSHINGS ON 600V DISCONNECT SWITCHES ON ROOF WHERE USING CONCENTRIC
INSULATING BUSHINGS REQUIRED ON CONNECTORS IN LIEBERT UNITS FOR #2 CONDUCTORS
6. DISCONNECTS NOT IN SIGHT FOR LIEBERTS
7. PROVIDE 8' LADDER FOR COMPUTER RM INSPECTION
01/03/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
- A REINSPECTION FEE IS ASSESSED,
PAY REFEE AT 201 N STONE PRIOR TO NEXT INSP.
- UNABLE TO CONDUCT INSP. DUE TO CONTR. OR COORDINATOR
12/28/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
MECHANICAL CONTRACTOR TO BE ON SITE FOR INSPECTION. LEAVE MESSAGE TO MEET WITH INSPECTOR. HAVE APPROVED PLANS ON SITE AND ALL EQUIPMENT OPEN FOR INSPECTION
TO AVOID REFEE @ NEXT INSPECTION PLEASE COMPLY
12/21/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PLANS/PERMIT MUST BE ON SITE
12/12/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- RECALL INSPECTION LEAVE MESSAGE FOR INSPECTOR
MEET ON SITE
- COULD NOT LOCATE CONTR. NOT ON SITE