Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM01517
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/21/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/23/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK LIST EXCEPT PANEL CRA REPLACE CHASE NIPPLE WITH CLOSE NIPPLE OR INSTALL LOCKNUT |
|
| 01/08/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. LABEL ALL PANELS, SCHEDULES, EQUIP. DISCONNECTS 2. PROVIDE OR INSTALL INSULATING BUSHING AT PANEL M3 FOR CONNECTOR AT TOP OF PANEL PER 300 NEC, #4 OR LARGER 3. OPEN J-BOX IN ELECTRIC ROOM FOR INSPECTION PROVIDE LIFT 4. MECH. LUGS NOT INSTALLED TO GROUND BUS PROPERLY IN "DB-S" CANNOT STACK ON TOP OF EXISTING LUGS. 5. INSTALL BOND BUSHINGS ON 600V DISCONNECT SWITCHES ON ROOF WHERE USING CONCENTRIC INSULATING BUSHINGS REQUIRED ON CONNECTORS IN LIEBERT UNITS FOR #2 CONDUCTORS 6. DISCONNECTS NOT IN SIGHT FOR LIEBERTS 7. PROVIDE 8' LADDER FOR COMPUTER RM INSPECTION |
|
| 01/03/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio - A REINSPECTION FEE IS ASSESSED, PAY REFEE AT 201 N STONE PRIOR TO NEXT INSP. - UNABLE TO CONDUCT INSP. DUE TO CONTR. OR COORDINATOR |
|
| 12/28/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* MECHANICAL CONTRACTOR TO BE ON SITE FOR INSPECTION. LEAVE MESSAGE TO MEET WITH INSPECTOR. HAVE APPROVED PLANS ON SITE AND ALL EQUIPMENT OPEN FOR INSPECTION TO AVOID REFEE @ NEXT INSPECTION PLEASE COMPLY |
|
| 12/21/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLANS/PERMIT MUST BE ON SITE |
|
| 12/12/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - RECALL INSPECTION LEAVE MESSAGE FOR INSPECTOR MEET ON SITE - COULD NOT LOCATE CONTR. NOT ON SITE |