Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/23/2008 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* #1 THRU #6 DUCT SMOKE DETECTORS TEST OK |
|
| 05/19/2008 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. FLEX DUCT NOT TO EXCEED 6' PER M2-8 2. BRANCH TAKE OFF's TO BE HIGH EFFICIENCY PER M2-8 3. VERIFY DAMPER IS IN WORKING ORDER AND NOT OBSTRUCTED IN EMPLOYEE LOUNGE |