Permit: T07CM01509

Parcel: 12510003F


Addresses:

3413 E BROADWAY BL


Inspection Status: Approved

Inspection History: OUTDOOR LIGHTING FINAL

Permit Number - T07CM01509

Inspection Description - OUTDOOR LIGHTING FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/17/2008 OUTDOOR LIGHTING FINAL Approved IVRS - Inspection :*
06/02/2008 OUTDOOR LIGHTING FINAL Not ready for Inspection INSPECTION FOR ROOFTOP ONLY - PARTIAL INSPECTION

1. IDENTIFY DATA PLATES ON RTU'S
2. PIPE CKT TO EX. FAN - NOT FLEX ALL THE WAY
3. SECURE EQUIPMENT TO STRUCTURE - NOT JUST BLOCKS
4. EQUIPMENT GROUNDS #6 & SMALLER TO HAVE GREEN INSULATION 250.119
5. FEEDS INTO UNITS FOR POWER AND RECEPTACLES TO HAVE RACEWAYS ALL THE WAY INTO THEIR J-BOXES
NO OPEN WIRING.