Permit: T07CM01509

Parcel: 12510003F


Addresses:

3413 E BROADWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/17/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/12/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. WIRING TO COMPACTOR NOT PER PLAN - NEED EXTERIOR DISCONNECT 2 GROUNDS UNDER SAME TERMINATION @ CONTROLLER? FLEX NOT TO BE USED WHERE SUBJECT TO PHYSICAL DAMAGE
2. INSTALL ALL SHELF LIGHTING & PROPERLY STRAP
06/06/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
WORK IN PROGRESS
06/05/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
WORK IN PROGRESS
06/03/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSPECTION FOR EMERGENCY LIGHTING ONLY

1. EMERGENCY LIGHTING NOT WORKING AND NOT PER PLAN

NOTE: SPACE NOT TO BE OCCUPIED BEFORE APPROVAL
06/02/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*