Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - OUTDOOR LIGHTING
Permit Number - T07CM01509
Inspection Description - ELECTRIC - OUTDOOR LIGHTING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/17/2008 | ELECTRIC - OUTDOOR LIGHTING | Approved | IVRS - Inspection :* | |
05/29/2008 | ELECTRIC - OUTDOOR LIGHTING | Not ready for Inspection | IVRS - Inspection :* PARTIAL INSPECTION 1. WIRE NUTS TO BE USED AS LISTED 2. HAVE OVERFILLED J-BOX 3. FIRE ALARM WIRING TO BE NEAT AND WORKMAN & L.V WIRING 4. SECURE EMT WITHIN 36" OF ENCLOSURES AND MAX. 10' 5. SELF TAP NOT ALLOWED FOR GROUND CONNECTION 6. CONDUCTORS TO BE PROPERLY DERATED |