Permit: T07CM01509

Parcel: 12510003F


Addresses:

3413 E BROADWAY BL

Inspection Status: Not Applicable

Inspection History: ELECTRIC - CONSTRUCTION POWER

Date Description Inspector Results Comments
06/17/2008 ELECTRIC - CONSTRUCTION POWER Not Applicable IVRS - Inspection :*
04/30/2008 ELECTRIC - CONSTRUCTION POWER Partial Approval IVRS - Inspection :*
OK TO ENERGIZE TEMPORARY POWER FOR SPIDER BOX ONLY.
DO NOT ENERGIZE OTHER WIRING BEFORE APPROVAL.
MAKE SURE ALL ENERGIZED EQUIPMENT IS CLOSED.
04/29/2008 ELECTRIC - CONSTRUCTION POWER Denied IVRS - Inspection :
See detailed listing on site.| 999*
04/25/2008 ELECTRIC - CONSTRUCTION POWER Not ready for Inspection IVRS - Inspection :*
WORK IN PROGRESS
04/22/2008 ELECTRIC - CONSTRUCTION POWER Not ready for Inspection IVRS - Inspection :*
NO INSPECTION AT THIS TIME, SINGLE LINE DIAGRAM TO BE REVISED TO REFLECT ACTUAL SCOPE OF WORK
04/15/2008 ELECTRIC - CONSTRUCTION POWER Not ready for Inspection IVRS - Inspection :*
1. CASH BOND TO BE POSTED WITH CITY OF TUCSON FOR POWER
2. HAVE TEMP POWER INSTALLED AND READY FOR INSPECTION AS IT WILL BE USED
3. AT SERVICE - INSTALL ADDRESS ON METER, BOND NEUTRAL TO SERVICE DISCONNECT ENCLOSURE, IDENTIFY SERVICE DISCONNECT
4. BOND STEEL & METAL PIPING TO SERVICE DISCONNECT ENCLOSURE