Permit: T07CM01509

Parcel: 12510003F


Addresses:

3413 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM01509

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/17/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
05/29/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/14/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
05/07/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER HARD LID & WING WALLS AT MAIN ENTRY
FOR HEATER/FIXTURES/ALARM
INSTALL NAIL PLATES, MIN. #10 TO HEATER, 2 MORE SCREWS
FOR HEATER INTO FRAMING
04/29/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL COVER INTERIOR FRAMED WALLS

1. NEED CORRECT SIZE BONDING CLAMP FOR PIPES -
NEC 110.3B
2. REMOVE PAINT UNDER LUGS TO STEEL - NEC 250.12
3. EMT TO BE ELECTRICALLY CONTINUOUS FOR G.E.C
NEC 250.62F
4. TIGHTEN ALL CONNECTIONS, PROVIDE TORQUE LETTER
5. CHECK TEMP WIRING