Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM01509
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/17/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
05/29/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
05/14/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
05/07/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER HARD LID & WING WALLS AT MAIN ENTRY FOR HEATER/FIXTURES/ALARM INSTALL NAIL PLATES, MIN. #10 TO HEATER, 2 MORE SCREWS FOR HEATER INTO FRAMING |
|
04/29/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALL COVER INTERIOR FRAMED WALLS 1. NEED CORRECT SIZE BONDING CLAMP FOR PIPES - NEC 110.3B 2. REMOVE PAINT UNDER LUGS TO STEEL - NEC 250.12 3. EMT TO BE ELECTRICALLY CONTINUOUS FOR G.E.C NEC 250.62F 4. TIGHTEN ALL CONNECTIONS, PROVIDE TORQUE LETTER 5. CHECK TEMP WIRING |