Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/17/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 05/16/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* HAVE WORK COMPLETED PRIOR TO CALL IN FOR INSPECTION |
|
| 05/02/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* AIR TEST DRAIN & VENT OK 1. SHALL SEE FINAL CONNECTION TO VENT & DRAIN SINGLE 1/2" WATER DROP FROM FIXTURE STUBBED INTO HALLWAY AIR TEST OK 2. SHALL PROVIDE BOTH WATER DROPS PER PLAN OR PROVIDE REVISED APPROVED PLAN OF YOUR INSTALLATION 3. 2" DRAIN ARM SHALL REQUIRE 2" P-TRAP FOR FIXTURE AT FINAL. 4. PIPING PASSING THRU FLOOR & WALLS REQUIRES CORRECT SEALING FOR APPLICATION NOTE: FIREWALL & FLOOR SEPARATIONS REQUIRE FIRE STOP SYSTEMS. |