Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM01507
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/01/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1. INSTALL 277V RATED SWITCH FOR LIGHTS AT RECEPTION 2. CANNOT TERMINATE GROUNDING CONDUCTORS ON NEUTRAL BAR. 3. UPDATE PANEL SCHEDULE. BE SPECIFIC NEC 408.4 4. CANNOT SECURE MC CABLE TO EMT AT PANEL 5. LABEL LIGHTING CIRCUIT AT PANEL 6. INSTALL BREAKERS LISTED FOR USE IN PANEL 7. INSTALL SEISMIC WIRES TO RECESSED FIXTURES. |