Permit: T07CM01507

Parcel: 12701005D

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM01507

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/01/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
1. INSTALL 277V RATED SWITCH FOR LIGHTS AT RECEPTION
2. CANNOT TERMINATE GROUNDING CONDUCTORS ON NEUTRAL BAR.
3. UPDATE PANEL SCHEDULE. BE SPECIFIC NEC 408.4
4. CANNOT SECURE MC CABLE TO EMT AT PANEL
5. LABEL LIGHTING CIRCUIT AT PANEL
6. INSTALL BREAKERS LISTED FOR USE IN PANEL
7. INSTALL SEISMIC WIRES TO RECESSED FIXTURES.