Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/15/2007 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* 1) PROVIDE CORRECT SIZE LUGS FOR #4 #1/0 IN CT CAN AND TIGHTEN |
|
| 11/13/2007 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BOND CONDUCTOR TO RISER UNDERSIZED NEC 250.66 2) TIGHTEN AND TORQUE ALL CONDUCTORS 3) INSTALL FUSES, INDENTIFY SERVICE DISCONNECTS 4) BOND FOR NIPPLE CT TO DISCONNECT UNDERSIZED 5) BOND FOR CT ENCLOSURE UNDERSIZED 6) NEED BUSHING FOR FEEDERS INTO PANEL (PLASTIC OK) |