Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
11/15/2007 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
1) PROVIDE CORRECT SIZE LUGS FOR #4 #1/0 IN CT CAN AND TIGHTEN
11/13/2007 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BOND CONDUCTOR TO RISER UNDERSIZED NEC 250.66
2) TIGHTEN AND TORQUE ALL CONDUCTORS
3) INSTALL FUSES, INDENTIFY SERVICE DISCONNECTS
4) BOND FOR NIPPLE CT TO DISCONNECT UNDERSIZED
5) BOND FOR CT ENCLOSURE UNDERSIZED
6) NEED BUSHING FOR FEEDERS INTO PANEL (PLASTIC OK)