Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
04/27/2009 ELECTRIC - UNDERGROUND Approved
11/30/2007 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
09/11/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
THIS STRUCTURE TO BE SUPPLIED BY ONLY ONE SERVICE UNLESS IT MEET THE EXCEPTIONS IN NEC 230.2 OR HAS A RATED WALL, MAKING IT AS TWO SEPARATE STRUCTURES.
PLANS NOT ON SITE.

OK PROVISIONAL COVER OF CATV, PHONE AND SERVICE SECONDARY RACEWAYS -

NOTE: A WARNING RIBBON IS TO BE INSTALLED MINIMUM 12" ABOVE SERVICE RACEWAY WHEN YOU BACKFILL