Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/05/2007 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 08/28/2007 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED APPROVED CHANGES 2. NEED GEC FOR X-FMR 3. NEUTRALS & GROUNDS TO BE SEPARATE AFTER TRANSFORMER 4. BONDING JUMPERS TO BE SIZED PROPERLY 5. INSTALL PROPER SIZE FUSES |
|
| 07/18/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1. OK PVC UNDERGROUND FROM SES TO BUILDING 2. PROTECT ELECTRICAL EQUIPMENT FROM DAMAGE TO EXPOSURE TO WEATHER -- NEC 110.11 3. INSTALL WARNING RIBBON ABOVE SERVICE ENTRANCE CONDUCTORS PER NEC 300.5 4. HAVE APPROVED SET OF DRAWINGS FOR CHANGES TO SES |