Permit: T07CM01490

Parcel: 135084520


Addresses:

7150 E 22ND ST 10

Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Date Description Inspector Results Comments
06/01/2007 ELECTRIC - UFER Approved IVRS - Inspection :*
05/31/2007 ELECTRIC - UFER Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. INSTALL GROUND CLAMP LISTED & MARKED FOR DIRECT BURY.
2. GROUND CLAMP ALSO TO BE MARKED FOR USE ON REBAR AND SIZE OF REBAR.
3. COULD NOT FIND SUCH MARKINGS ON INSTALLED GROUND CLAMPS.