Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM01488
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/05/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/29/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* RECALL AFTER LIFTS INSTALLED |
|
08/28/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. NEED APPROVED CHANGES 2. NEED GEC FOR XFMR 3. NEUTRALS & GROUNDS TO BE SEPARATE AFTER TRANSFORMER 4. BONDING JUMPERS TO BE SIZED PROPERLY 5. TURN POWER ON & RECALL FOR FINAL |
|
08/23/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
08/22/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no plan or job inspection card on site.| 925* 1. NO ONE ON SITE LEFT MESSAGE FOR BRIAN WAS ON THE WAY 2. HAVE APPROVED SET OF PLANS ON SITE 3. HAVE SOMEONE ON SITE TO OPEN ELECTRICAL EQUIPMENT |