Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/22/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/18/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED DISCONNECTING MEANS FOR INSTA-HOT NEC 422.31 B 2. BRANCH CKT AND BREAKER TO BE 30 AMP (#10 CU WIRE & 30 AMP BREAKER) -- NEC 422 3. PANEL DIRECTORIES TO BE LEGIBLE AND CORRECT NEC 408.4 |