Permit: T07CM01461

Parcel: 10406011E

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM01461

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/22/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/18/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED DISCONNECTING MEANS FOR INSTA-HOT
NEC 422.31 B
2. BRANCH CKT AND BREAKER TO BE 30 AMP (#10 CU WIRE & 30 AMP BREAKER) -- NEC 422
3. PANEL DIRECTORIES TO BE LEGIBLE AND CORRECT
NEC 408.4