Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/15/2007 | FRAMING | Approved | IVRS - Inspection :* | |
| 06/11/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO HOLDOWN BOLT EPOXY NOT DONE 2) OK TO INSULATE |
|
| 06/06/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) HOLDOWNS MISSING ANCHOR BOLTS 2) EXTERIOR WALL NOT APPROVED 3) HAVE ENGINEER PROVIDE DESIGN FOR HU26-2 ATTACHMENT TO OPEN WEB FLOOR TRUSS 4) OVERNOTCHED BEARING STUDS MAX NOTCH ALLOWED 25 PERCENT 5) HAVE ENGINEER OF RECORD SPECIFY DESIGN FOR RETRO FIT HOLDOWNS 6) PLUMBING AND ELECTRIC OUT OF WALL ? |