Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/09/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/02/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* ON ROOFTOP 1. NEED MINIMUM #10 CU FOR 30 AMP EQUIPMENT GROUND NEC 250.122 2. EQUIPMENT GROUNDS #6 AND SMALLER TO BE GREEN OR BARE ENTIRE LENGTH - 250.119 3. SPLIT BOLTS NOT USED PER THEIR LISTING IN GUTTER - 110.3B 4. 2 STRANDED NOT ALLOWED UNDER LUG IN GUTTER - 110.3B SAME LUG TO HAVE FULL CONTACT 5. TIGHTEN BOND SCREWS IN DISCONNECTS 6. IDENTIFY ALL DISCONNECTS HP1, HP2 ETC. - NEC 110 7. GROUND TO GUTTER UNDERSIZED - NEC 250.122C 8. A SERVICE RECEPTACLE IS REQUIRED WITHIN 25' OF UNITS NEC 210.63 9. REVISE PANEL DIRECTORIES TO BE COMPLETE & CORRECT NEC 408.4 10. HP5 MISSING HEAT STRIPS AND SERVICE RECEPTACLE |
|
| 10/01/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLANS TO BE ON SITE 2. ELECTRICIAN TO BE ON SITE |