Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/21/2008 | PLUMBING - FINAL | Approved | IVRS - Inspection :* RECEIVED (4) IN HOUSE BACKFLOW CERTIFICATIONS |
|
| 02/20/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* DRAINS FROM FOOT SPAS TO HAVE MINIMUM 1" AIR GAP AND BE FULL SIZE DISCHARGE PIPING, ALL FIXTURES TO BE FUNCTIONAL - SEE ALL NOTES FROM 1/31/08 AND COMPLY |
|
| 02/12/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* UNABLE TO DECIPHER PHONE NUMBER --- DOOR LOCKED |
|
| 01/31/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. AT LAVATORY - TAILPIECE TO HAVE A SMOOTH INTERIOR WATER WAY 2. EXTEND CLEANOUTS AND FINISH PROPERLY 3. NO GRATE OR STRAINER AT FLOOR SINK 4. PEX NOT APPROVED FIXTURE CONNECTOR 5. H/C WATER CLOSET TO HAVE FLUSH HANDLE ON WIDE SIDE LAV FCT TO BE H/C RATED |