Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM01424

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/30/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/28/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SINGLE LINE DIAGRAM DOES NOT REFLECT ACTUAL SERVICE EXISTING SERVICE HAS FOUR SERVICE DISCONNECTS
2. SERVICE DISCONNECT ENCLOSURE FOR THIS SPACE IS MISSING ITS DEAD FRONT COVER
3. IDENTIFY "SERVICE DISCONNECT" AS SUCH AND INSTALL ADDRESS LABEL - SHARPIE NOT ALLOWED
4. FEEDER EQUIPMENT GROUNDING CONDUCTOR TO BE GREEN ENTIRE LENGTH
5. NEED SQ.D HOMELINE BREAKER FOR AC CKT
6. REMOVE BONDING SCREW IN SUB-PANEL
7. EMERGENCY EXIT SIGNS NOT WORKING/NO POWER
8. PANEL DIRECTORY TO BE CORRECT, LEGIBLE
9. TIGHTEN ALL EMT FITTINGS

DO NOT CALL BEFORE ALL COMPLETE
04/15/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. REVISED PLAN DOES NOT SHOW ACTUAL SCOPE OF WORK SINGLE LINE DIAGRAM NOT CORRECT
2. LICENSED ELECTRICAL CONTRACTOR RESPONSIBLE FOR THIS JOB TO BE ON SITE FOR INSPECTION
3. REPAIR TO G.E.C TO BE OPEN FOR INSPECTION
01/31/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED PANEL DIRECTORY
2. RECEPTACLE UNDER PANEL MISSING GROUND
3. REPLACE PAINTED OVER RECEPTACLES
4. REPLACE BROKEN RECEPTACLE PLATES
5. REVISE PLAN FOR NEW PANEL BEING INSTALLED
6. SEAL OPEN KNOCK OUT IN LIGHT FIXTURE
7. PLAN CALLS FOR LIGHTED EXIT @ FRONT DOOR & BACK DOOR
8. INSTALL DISCONNECT FOR WATER HEATER. SEE PLAN.
9. LARGE LUG ON GROUND BAR NOT RATED FOR #12
10. BONDING JUMPER NOT SIZED PROPERLY TO BOND BUSHING TO BE #10
11. GROUNDING ELECTRODE CONDUCTOR CUT & MISSING @ SERVICE
12. PLAN CALLS FOR INTERLOCKING OF A/C UNIT & EXHAUST FAN - WHERE IS THIS?
13. PROVIDE LADDER FOR ROOF ACCESS
14. COMPLY WITH PREVIOUS INSPECTION ITEMS