Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM01424
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/30/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/28/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SINGLE LINE DIAGRAM DOES NOT REFLECT ACTUAL SERVICE EXISTING SERVICE HAS FOUR SERVICE DISCONNECTS 2. SERVICE DISCONNECT ENCLOSURE FOR THIS SPACE IS MISSING ITS DEAD FRONT COVER 3. IDENTIFY "SERVICE DISCONNECT" AS SUCH AND INSTALL ADDRESS LABEL - SHARPIE NOT ALLOWED 4. FEEDER EQUIPMENT GROUNDING CONDUCTOR TO BE GREEN ENTIRE LENGTH 5. NEED SQ.D HOMELINE BREAKER FOR AC CKT 6. REMOVE BONDING SCREW IN SUB-PANEL 7. EMERGENCY EXIT SIGNS NOT WORKING/NO POWER 8. PANEL DIRECTORY TO BE CORRECT, LEGIBLE 9. TIGHTEN ALL EMT FITTINGS DO NOT CALL BEFORE ALL COMPLETE |
|
04/15/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. REVISED PLAN DOES NOT SHOW ACTUAL SCOPE OF WORK SINGLE LINE DIAGRAM NOT CORRECT 2. LICENSED ELECTRICAL CONTRACTOR RESPONSIBLE FOR THIS JOB TO BE ON SITE FOR INSPECTION 3. REPAIR TO G.E.C TO BE OPEN FOR INSPECTION |
|
01/31/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED PANEL DIRECTORY 2. RECEPTACLE UNDER PANEL MISSING GROUND 3. REPLACE PAINTED OVER RECEPTACLES 4. REPLACE BROKEN RECEPTACLE PLATES 5. REVISE PLAN FOR NEW PANEL BEING INSTALLED 6. SEAL OPEN KNOCK OUT IN LIGHT FIXTURE 7. PLAN CALLS FOR LIGHTED EXIT @ FRONT DOOR & BACK DOOR 8. INSTALL DISCONNECT FOR WATER HEATER. SEE PLAN. 9. LARGE LUG ON GROUND BAR NOT RATED FOR #12 10. BONDING JUMPER NOT SIZED PROPERLY TO BOND BUSHING TO BE #10 11. GROUNDING ELECTRODE CONDUCTOR CUT & MISSING @ SERVICE 12. PLAN CALLS FOR INTERLOCKING OF A/C UNIT & EXHAUST FAN - WHERE IS THIS? 13. PROVIDE LADDER FOR ROOF ACCESS 14. COMPLY WITH PREVIOUS INSPECTION ITEMS |