Permit: T07CM01411

Parcel: 141316900


Addresses:

7767 E JACK OAK RD


Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T07CM01411

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
06/20/2007 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
06/08/2007 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) 1,024 POUNDS ON HANGER AT G01-2 PLY TRUSS VERIFY HANGER TYPE (USP HUS) NOT FOUND IN USP CATALOG
2) NEED RAT RUN ON A02 TRUSSES, A02GE-TRUSS AT GARAGE INTERIOR
3) NEED H2.5 AT GARAGE LEDGER OR COMPLY WITH BENT OVER A3.5 1/A2
4) WRONG HANGERS 1327 LOAD, 1320 MAX CAPACITY HANGER