Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T07CM01411
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/20/2007 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 06/08/2007 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) 1,024 POUNDS ON HANGER AT G01-2 PLY TRUSS VERIFY HANGER TYPE (USP HUS) NOT FOUND IN USP CATALOG 2) NEED RAT RUN ON A02 TRUSSES, A02GE-TRUSS AT GARAGE INTERIOR 3) NEED H2.5 AT GARAGE LEDGER OR COMPLY WITH BENT OVER A3.5 1/A2 4) WRONG HANGERS 1327 LOAD, 1320 MAX CAPACITY HANGER |