Permit: T07CM01410

Parcel: 14043011A

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T07CM01410

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/10/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
DUCT SMOKE DETECTOR TESTED OK SEE BUILDING INSPECTOR FOR C OF O
02/28/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
PROVIDE DUCT SMOKE DETECTOR ON UNIT OVER 2000 CFM
01/23/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
STRAP FLEX AS NEEDED, LOT TO EXCEED 5'
STENCIL E.D DOORS
PROVIDE SECONDARY DRAIN ON #2 UNIT, CLAMP PRIMARY
L.VOLTAGE MUST BE PROTECTED ON EXTERIOR