Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CONSTRUCTION POWER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/20/2008 | ELECTRIC - CONSTRUCTION POWER | Approved | IVRS - Inspection :* | |
| 12/18/2007 | ELECTRIC - CONSTRUCTION POWER | Partial Approval | IVRS - Inspection :* 1. BOND BLD STEEL, WATER, GAS, X-FORMER 2. COMPLETE FIXTURE SEISMIC WIRES 3. MAIN BOND JUMPER FOR SERVICE DISCONNECT 4. RECEIVED LETTER FOR USE OF MC CABLE |
|
| 11/06/2007 | ELECTRIC - CONSTRUCTION POWER | Partial Approval | IVRS - Inspection :* - OK WALLS FOR OFFICE RESTROOMS, STORAGE - PLEASE HAVE PERMITTING ADD 2035, 2036 TO PERMIT FOR INTERMEDIATE & ELECTRIC ABOVE CEILING |
|
| 09/05/2007 | ELECTRIC - CONSTRUCTION POWER | Denied | IVRS - Inspection : See detailed listing on site.| 999* |