Permit: T07CM01410

Parcel: 14043011A

Inspection Status: Approved

Inspection History: ELECTRIC - CONSTRUCTION POWER

Date Description Inspector Results Comments
02/20/2008 ELECTRIC - CONSTRUCTION POWER Approved IVRS - Inspection :*
12/18/2007 ELECTRIC - CONSTRUCTION POWER Partial Approval IVRS - Inspection :*
1. BOND BLD STEEL, WATER, GAS, X-FORMER
2. COMPLETE FIXTURE SEISMIC WIRES
3. MAIN BOND JUMPER FOR SERVICE DISCONNECT
4. RECEIVED LETTER FOR USE OF MC CABLE
11/06/2007 ELECTRIC - CONSTRUCTION POWER Partial Approval IVRS - Inspection :*
- OK WALLS FOR OFFICE RESTROOMS, STORAGE
- PLEASE HAVE PERMITTING ADD 2035, 2036 TO PERMIT FOR INTERMEDIATE & ELECTRIC ABOVE CEILING
09/05/2007 ELECTRIC - CONSTRUCTION POWER Denied IVRS - Inspection :
See detailed listing on site.| 999*