Permit: T07CM01410

Parcel: 14043011A

Inspection Status: Approved

Inspection History: SHEET ROCK NAILING

Date Description Inspector Results Comments
02/29/2008 SHEET ROCK NAILING Approved IVRS - Inspection :*
11/29/2007 SHEET ROCK NAILING Partial Approval IVRS - Inspection :*
1. YOU MUST PROVIDE FIRESTOP SYSTEM FOR ALL PENETRATIONS OF 2 & 3 HR WALLS
2. OK TO TAPE - EXCEPT DO NOT TAPE AROUND PENETRATIONS
11/15/2007 SHEET ROCK NAILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. WHAT KIND OF FIRESTOP SYSTEM WILL YOU USE?
2. FIRE BARRIERS MAY HAVE NO MORE THAN 1/8" GAP AT JOINTS AND YOU MAY NOT MAKE HOLES WITH A HAMMER USE A SAW.