Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM01401
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/07/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK FINAL |
|
04/15/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. FINISH #4 OF PREVIOUS INSPECTION 2. AS BUILT REVISIONS NOT AS BUILT |
|
03/31/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. LABEL EQUIPMENT ON OUTSIDE OF COVERS 2. NEED CIRCUIT DIRECTORY 3. MAINTAIN 6' CLEARANCE AT TRANSFORMER 4. PLEASE RESOLVE ITEMS REGARDING MAIN 800 AMP BREAKERS AND PLAN REVISIONS WITH CITY APPROVAL STAMPS |
|
03/28/2008 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled | |
03/24/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. VERIFY LUG TO CONDUCTOR SIZES FOR GROUNDS OK CONDUITS OK EQUIPMENT TO CROSSOVER |
|
01/18/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
01/14/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FINISH PREVIOUS ITEMS #1, PHASE 1 #1, 5 AND 8 PHASE 2 |
|
01/08/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. HAVE ENGINEER OF RECORD VERIFY IF BREAKER INSTALLED IS AS REQUESTED 2. CORRECTLY INSTALL ISOLATED GROUNDING SYSTEM 3. LABELING TO BE AS PER PLANS 4. TIGHTEN LOOSE FITTINGS 5. USE APPROVED REDUCING MATERIALS 6. CLEAN TRASH FROM UNDER FLOOR 7. FINISH PREVIOUS ITEMS 7, 8, 11 8. LABELING PER 210.5(C) FOR CONDUCTORS IS NEEDED |