Permit: T07CM01401

Parcel: 12701003K

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM01401

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/07/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
03/28/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
RECEIVED GENERATOR TEST REPORT
01/18/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK PHASE 1 AS DISCUSSED
01/10/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. BEAM CLAMP NOT LISTED FOR GROUNDING
2. FINISH ISOLATED GROUND SYSTEM AS PER ENGINEERS INSTRUCTIONS
12/20/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) WILL NEED RE-CLEARANCE WHEN 800 AMP MAIN IS INSTALLED
12/18/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1 PHASE NEUTRAL CONDUCTOR DAMAGED
12/13/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. GROUNDING ELECTRODE CONDUCTOR CONNECTION TO BE ACCESSIBLE
2. BONDING JUMPER TO BE AS PER 250.102, 250.66
3. HUBS TO BE LISTED FOR BONDING - 250.92, 110.3
4. INSTALL MAIN BONDING JUMPER
5. BREAKER FOR MAIN IS 700 AMPS - PLANS CALL FOR 800 AMP
6. CANNOT STACK LUGS - PROVIDE SURFACE CONTACT
7. TIGHTEN LUGS
8. SECURE TRANSFORMER TO STRUCTURE
9. INSTALL SET SCREW ON BUSHING
10. SEPARATE GROUNDING & GROUNDED BARS AT SUB-PANEL
11. CONDUCTOR TO BE AS PER 210.5 (C) AMENDMENTS
12. HAVE BUILDING INSPECTOR LOOK AT FIRE STOPPING

*DO NOT ENERGIZE PANELS WITHOUT INSPECTIONS
12/03/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 3 - 4" CONDUITS FROM 800A DISCONNECT OUTSIDE TO
800 AMP SWITCHBOARD ELECTRIC ROOM
2ND FLOOR - SUBJECT TO APPROVED PLAN