Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM01401
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/07/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
03/28/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* RECEIVED GENERATOR TEST REPORT |
|
01/18/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK PHASE 1 AS DISCUSSED |
|
01/10/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. BEAM CLAMP NOT LISTED FOR GROUNDING 2. FINISH ISOLATED GROUND SYSTEM AS PER ENGINEERS INSTRUCTIONS |
|
12/20/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) WILL NEED RE-CLEARANCE WHEN 800 AMP MAIN IS INSTALLED |
|
12/18/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1 PHASE NEUTRAL CONDUCTOR DAMAGED |
|
12/13/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. GROUNDING ELECTRODE CONDUCTOR CONNECTION TO BE ACCESSIBLE 2. BONDING JUMPER TO BE AS PER 250.102, 250.66 3. HUBS TO BE LISTED FOR BONDING - 250.92, 110.3 4. INSTALL MAIN BONDING JUMPER 5. BREAKER FOR MAIN IS 700 AMPS - PLANS CALL FOR 800 AMP 6. CANNOT STACK LUGS - PROVIDE SURFACE CONTACT 7. TIGHTEN LUGS 8. SECURE TRANSFORMER TO STRUCTURE 9. INSTALL SET SCREW ON BUSHING 10. SEPARATE GROUNDING & GROUNDED BARS AT SUB-PANEL 11. CONDUCTOR TO BE AS PER 210.5 (C) AMENDMENTS 12. HAVE BUILDING INSPECTOR LOOK AT FIRE STOPPING *DO NOT ENERGIZE PANELS WITHOUT INSPECTIONS |
|
12/03/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 3 - 4" CONDUITS FROM 800A DISCONNECT OUTSIDE TO 800 AMP SWITCHBOARD ELECTRIC ROOM 2ND FLOOR - SUBJECT TO APPROVED PLAN |