Permit: T07CM01391

Parcel: 12702234B


Addresses:

5140 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM01391

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/04/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/01/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
ROOF:
1. RECEPTACLE COVER TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO - 406.8
2. LABEL DISCONNECTS
3. TIGHTEN LOOSE FITTINGS
4. ONLY ONE CONDUCTOR PER LUG TERMINATION
5. GROUNDING EQUIPMENT CONDUCTOR TO BE GREEN ENTIRE LENGTH - 250.119
6. MAINTAIN RECEPTACLE TO BE WITHIN 25' OF UNIT 210.63
03/28/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
PLEASE PROVIDE ROOF ACCESS TO INSPECT
PHONE NUMBER ON MESSAGE DID NOT WORK