Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM01391
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/04/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/01/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* ROOF: 1. RECEPTACLE COVER TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO - 406.8 2. LABEL DISCONNECTS 3. TIGHTEN LOOSE FITTINGS 4. ONLY ONE CONDUCTOR PER LUG TERMINATION 5. GROUNDING EQUIPMENT CONDUCTOR TO BE GREEN ENTIRE LENGTH - 250.119 6. MAINTAIN RECEPTACLE TO BE WITHIN 25' OF UNIT 210.63 |
|
| 03/28/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* PLEASE PROVIDE ROOF ACCESS TO INSPECT PHONE NUMBER ON MESSAGE DID NOT WORK |