Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM01391
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/04/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 03/05/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. PLEASE POST BOND FOR TEMP POWER FOR TEST 2. INSTALL BREAKERS & TERMINATE CONDUCTORS 3. PANEL MORE THAN 1/4" FROM CAN TO SURFACE 4. ADD 02062 TO PERMIT |
|
| 01/18/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS |
|
| 01/17/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO INSULATE 1. BOND BUILDING STEEL AS PER PLANS & CODE 2. MOVE M/C OUT OF SHALLOW STUD CHANNEL |
|
| 01/07/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PROTECT M/C CABLE INSIDE OF SHALLOW STUD CHANNELS ALSO, REGULAR STUD CHANNELS 2. SUPPORT VDV CABLING IN WALL 725.6 3. GROUND RODS TO BE INSTALLED AS PER CODE 250.53 4. INSTALL REJECTION PINS & FUSES 5. NEED PERMANENT METAL ADDRESS LABEL 6. SERVICES IN THE AREA ARE UNDERGROUND - NEW SERVICES TO BE UNDERGROUND - APPLY FOR WAIVER 7. NO PLANS ON SITE |