Permit: T07CM01391

Parcel: 12702234B


Addresses:

5140 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM01391

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
04/04/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
03/05/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. PLEASE POST BOND FOR TEMP POWER FOR TEST
2. INSTALL BREAKERS & TERMINATE CONDUCTORS
3. PANEL MORE THAN 1/4" FROM CAN TO SURFACE
4. ADD 02062 TO PERMIT
01/18/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS
01/17/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO INSULATE
1. BOND BUILDING STEEL AS PER PLANS & CODE
2. MOVE M/C OUT OF SHALLOW STUD CHANNEL
01/07/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PROTECT M/C CABLE INSIDE OF SHALLOW STUD CHANNELS ALSO, REGULAR STUD CHANNELS
2. SUPPORT VDV CABLING IN WALL 725.6
3. GROUND RODS TO BE INSTALLED AS PER CODE 250.53
4. INSTALL REJECTION PINS & FUSES
5. NEED PERMANENT METAL ADDRESS LABEL
6. SERVICES IN THE AREA ARE UNDERGROUND -
NEW SERVICES TO BE UNDERGROUND - APPLY FOR WAIVER
7. NO PLANS ON SITE