| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/24/2007 | ELECTRIC - CONSTRUCTION POWER | Partial Approval | IVRS - Inspection :* 1. BACK FED MAIN BREAKER TO HAVE MANUFACTURES HOLDDOWN. 2. SHEETMETAL SCREWS NOT ALLOWED 250.8 GROUND BAR 3. FINISH #5 OF INSPECTION DATED 5/18/07 |
|
| 05/23/2007 | ELECTRIC - CONSTRUCTION POWER | Not ready for Inspection | IVRS - Inspection :* | |
| 05/21/2007 | ELECTRIC - CONSTRUCTION POWER | Partial Approval | IVRS - Inspection :* OK UNDERGROUND |
|
| 05/18/2007 | ELECTRIC - CONSTRUCTION POWER | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. XHHW-2 CONDUCTORS NOT MARKED FOR DIRECT BURIAL INSTALL CONDUCTORS LISTED FOR DIRECT BURIAL OR PROVIDE LISTING OF INSTALLED CONDUCTORS. 2. GROUND RODS TO BE MIN. 6' APART 3. RACEWAYS (PVC) PROTECTING DIRECT BURIAL WIRES TO GO MIN. 18 IN. BELOW GRADE. 4. SECURE PVC RISER TO TRAILER 5. INSTALL PLASTIC BUSHINGS ON PVC CONNECTORS WHERE CABLES #4 & LARGER ARE INSTALLED PER NEC 352.46 & 300.4 |