Permit: T07CM01389

Parcel: 119180860


Addresses:

3702 S 16TH AV


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T07CM01389

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/27/2007 MECHANICAL - FINAL Approved
07/24/2007 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
PROVIDE AIR BALANCE REPORT
07/23/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
PROVIDE AIR BALANCE REPORT
NEED TO TEST DUCT SMOKE DETECTORS
OK TO FILE FOR TEMP C OF O
07/20/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. PAINT EXPOSED PVC W/LATEX PAINT. PROVIDE A ROOF JACK AT ROOF PENETRATION.
2. PERMANENTLY I.D EQUIPMENT UNIT NUMBER & ADDRESS
3. PROVIDE COVER OVER CANVAS CONNECTOR
4. SOUTH A/C LEAKING CONDENSATE ON THE ROOF
5. NEW A/C DISCONNECT OVERFUSED
6. PROVIDE REQUIRED SERVICE RECEPTACLES
7. PROVIDE A FRESH AIR INTAKE ON THE CARRIER UNIT
8. PROVIDE AIR BALANCE
9. PRE-TEST ALL DUCT SMOKE DETECTORS
07/19/2007 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*