Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/27/2007 | MECHANICAL - FINAL | Approved | ||
| 07/24/2007 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* PROVIDE AIR BALANCE REPORT |
|
| 07/23/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PROVIDE AIR BALANCE REPORT NEED TO TEST DUCT SMOKE DETECTORS OK TO FILE FOR TEMP C OF O |
|
| 07/20/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. PAINT EXPOSED PVC W/LATEX PAINT. PROVIDE A ROOF JACK AT ROOF PENETRATION. 2. PERMANENTLY I.D EQUIPMENT UNIT NUMBER & ADDRESS 3. PROVIDE COVER OVER CANVAS CONNECTOR 4. SOUTH A/C LEAKING CONDENSATE ON THE ROOF 5. NEW A/C DISCONNECT OVERFUSED 6. PROVIDE REQUIRED SERVICE RECEPTACLES 7. PROVIDE A FRESH AIR INTAKE ON THE CARRIER UNIT 8. PROVIDE AIR BALANCE 9. PRE-TEST ALL DUCT SMOKE DETECTORS |
|