Inspection Status: Approved
Inspection History: BUILDING - PROGRESS
Permit Number - T07CM01389
Inspection Description - BUILDING - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/25/2007 | BUILDING - PROGRESS | Approved | PER BU FINAL | |
07/06/2007 | BUILDING - PROGRESS | Denied | PROVIDE CORRECT CODE ANALYSIS FOR ENTIRE BUILDING. LISTED BUILDING TYPE (IIB/AS) IS INCORRECT BUILDING APPEARS TO BE IIIB OR VB NON-SPRINKLERED. CODE ANALYSIS MUST INCLUDE AREA OF ENTIRE BUILDING; IF SEPERATED USE THEN WE NEED TO KNOW ADJACENT TENANTS; IF NON-SEPERATED USE THEN CODE ANALYSIS MUST REFLECT MOST RESTRICTIVE OCCUPANCY. |