Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/27/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 06/01/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* CANCELLED |
|
| 05/31/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO TILE |
|
| 05/29/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1. WE HAVE BOX CONDUCTOR OVERFILL 2. SUPPORT WIRES NEEDED FOR FIXTURE - CANS 3. SUPPORT EXISTING & NEW VDV CABLING AS PER 725.3 & 6 AND 800.3 & 6 4. SUPPORT M/C CABLE WITHIN 12" OF CANS & EXHAUST FANS 5. USE APPROVED & LISTED STRAPS FOR M/C CABLE 6. JUNCTION BOXES TO BE ACCESSIBLE |