Permit: T07CM01366

Parcel: 133398300

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM01366

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/15/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/24/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. LABEL CIRCUITS AT PANEL NEC 408.4
2. INSTALL BREAKERS LISTED FOR USE IN SIEMENS PANEL
NEC 110.3
3. BOXES FOR RECEPTACLE/SWITCHES CANNOT BE SET BACK MORE THAN 1/4" FROM FINISHED SERVICE. INSTALL EXTENSION RINGS - NEC 314.20
4. INSTALL DISCONNECTING MEANS AT RAMADA FOR CIRCUIT FEEDING RAMADA - NEC 225.31, 225.32, 225.36
05/30/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. RECALL FOR FINAL WHEN ALL WORK COMPLETE
2. FOR GAS LINE NEED REVISION TO ACTIVITY & CAN BE INSTALLED IN SAME TRENCH WITH ELECTRIC.