Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/10/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/05/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ON ROOF - SECURE CU-1 UNIT & RACEWAY TO ROOF, GROUND SCREW STRIPPED IN DISCONNECT, MISSING K.O IN J-BOX 2. IDENTIFY DISCONNECTS WITH METAL TAG, NOT SHARPIE 3. PROVIDE GFI PROTECTION FOR ROOFTOP SERVICE RECEPTACLES. 4. CEILING LOW VOLTAGE WIRING TO BE PROPERLY SUPPORTED AND RAN IN A NEAT AND WORKMANLIKE MANNER BOXES THAT CONTAIN FIRE ALARM TERMINATIONS NEED TO BE RED IN COLOR 5. INSTALL NEW WEATHERPROOF COVER ON 2 GANG EXTERIOR BOX BY SERVICE WALKWAY |
|
| 10/04/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PARTIAL INSPECTION-GET LETTER CONCERNING HEAT STRIPS 2) FINISH ALARM WIRING 3) CALL BACK TO CONTINUE FINAL INSPECTION |
|
| 09/14/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* LOCKED NO ACCESS |